Simultaneous firing system delivers £30k annual saving
JBC designed, installed, modified and commissioned an upgrade from an existing 6000 digital burner modulation system to an ‘Ecosafe’ 6009 simultaneous firing system. The upgrade increased the amount of biogas burned by 25%, saving the company £30k per year!.

The required components were retrofit and the panel modified to allow a Hamworthy burner to operate and burn the maximum methane produced.
The system required a different controller and a second oxygen probe as well as replacing the methane metering valve. Two analogue outputs were also supplied, one for modulating/firing rate and another for available bio gas. A digital run signal allowed the customer to monitor boiler firing time and also where in the modulation range the burner operated.
Once complete, the installation was tested and demonstrated before the final hand over to the customer.